Capillary Length | : | 36 in |
Connection Type | : | 1/4 in Flared Nut |
Contact Rating | : | 16 A Full Load, 96 A Locked Rotor, 16 A Non-Inductive at 120 VAC, 9.2 A Full Load, 55.2 A Locked Rotor, 9.2 A Non-Inductive at 208 VAC, 8 A Full Load, 48 A Locked Rotor, 8 A Non-Inductive at 240 VAC, 7 A Full Load, 42 A Locked Rotor, 7 A Non-Inductive at 277 VAC, Pilot-Duty - 125 V-A at 24 VAC, 720 V-A at 120 - 277 VAC |
Pressure Rating | : | Low Pressure Side - 12 inHg to 80 lb/sq-in, 5 lb/sq-in Minimum - 35 lb/sq-in Maximum Adjustable Differential, High Pressure Side - 100 to 500 lbf/sq-in |
Series | : | P70 Series |
Switching Action | : | (2) SPDT |
Voltage Rating | : | 120/208/240/244 VAC |
Johnson Controls Penn Dual Pressure Control, P70 Series, 120/208/240/244 VAC, 1/4 in Flared Nut Connection, (2) SPDT Switching Action, Low Pressure Side - 12 inHg to 80 lb/sq-in, 5 lb/sq-in Minimum - 35 lb/sq-in Maximum Adjustable Differential, High Pressure Side - 100 to 500 lbf/sq-in, 16 A Full Load, 96 A Locked Rotor, 16 A Non-Inductive at 120 VAC, 9.2 A Full Load, 55.2 A Locked Rotor, 9.2 A Non-Inductive at 208 VAC, 8 A Full Load, 48 A Locked Rotor, 8 A Non-Inductive at 240 VAC, 7 A Full Load, 42 A Locked Rotor, 7 A Non-Inductive at 277 VAC, Pilot-Duty - 125 V-A at 24 VAC, 720 V-A at 120 - 277 VAC Contact Rating, 36 in Capillary Length
- All steel case and cover - built to provide long-lasting, rugged protection for internal components
- Compatible with non-corrosive refrigerants
- Fixed differential at 65 lbf/sq-in or lockout requires manual reset