ICP™ RHS120H0AA0AAA Package Rooftop Heat Pump, 10 ton Nominal, 116000 Btu/hr Heating BTU, 208/230 VAC, 47 A

ICP™ RHS120H0AA0AAA Package Rooftop Heat Pump, 10 ton Nominal, 116000 Btu/hr Heating BTU, 208/230 VAC, 47 A

Brand: ICP™
Part #: 12987
Customer Part #:
Amperage Rating      :      47 A
CFM Rating      :      2350 cfm
Coil Rating      :      Evaporator Coil - 11.1 sq-ft Face Area, 15 Fins/in, Condenser Coil - 25.1 sq-ft Face Area, 17 Fins/in
Compressor Type      :      Scroll
Connection Type      :      3/4 in Condensate Drain
Cooling BTU Rating      :      117000 Btu/hr Cooling
Dimensions      :      59-1/2 in W x 88-1/8 in D x 49-3/8 in H
EER Rating      :      11
Finish      :      Pre-Painted Baked Enamel
Frequency Rating      :      60 Hz
Fuse Rating      :      60 A
HP Rating      :      1/4 hp
Heating BTU Rating      :      116000 Btu/hr Heating
Material      :      Galvanized Steel
Model      :      RHS120
Nominal Capacity      :      10 ton
Number of Stages      :      2
Phase      :      3 ph
Refrigerant Type      :      R-410A
Series      :      RHS
Sound Level      :      87 dBA
Voltage Rating      :      208/230 VAC

ICP™ Package Rooftop Heat Pump, Series: RHS, Model: RHS120, 10 ton Nominal Capacity, 117000 Btu/hr Cooling BTU, 116000 Btu/hr heating BTU, 208/230 VAC, 47 A, 1/4 hp, 60 Hz, 3 ph Phase, Scroll Compressor, 2350 cfm, 11 EER Rating, 3/4 in Condensate Drain Connection, R-410A Refrigerant, 2 Stages, 60 A Fuse Rating, 87 dBA Sound Level, Evaporator Coil - 11.1 sq-ft Face Area, 15 Fins/in, Condenser Coil - 25.1 sq-ft Face Area, 17 Fins/in Coil Rating, Galvanized Steel, Pre-Painted Baked Enamel, 59-1/2 in W x 88-1/8 in D x 49-3/8 in H

  • (A) standard static motor - belt drive
  • Aluminum/copper - condenser/evaporator coil configuration
  • Standard single speed indoor fan motor
  • Exclusive non-corrosive composite condensate pan in accordance with ASHRAE 62 standard, sloping design, side or center drain
  • Convertible from vertical to horizontal air flow for slab mounting
  • Pre-printed exterior panels and tested to 500 hr salt spray protection
  • Fixed orifice refrigerant metering system
  • Cooling operating range upto 115 deg F and down to 25 deg F
  • Solid-state control board and easy access terminal board
  • Refrigerant filter drier and accumulator on each refrigerant circuit
  • Automatic changeover when used with auto changeover thermostat
  • Access panels with easy grip handles
  • Innovative, easy starting, no strip screw features on unit access panels
  • 2 in disposable return air filters with tool less filter access door
  • Belt drive evaporator fan motor and pulley combinations
  • New terminal board facilitating simple safety circuit trouble-shooting and simplified control box arrangement
  • Thru-the-bottom power entry capability standard
  • One-point electrical connections
  • Full perimeter base rail with built-in rigging adapters and fork truck slots
  • Scroll compressors with internal line break overload protection