This is an alert about new products, services, trainings, jobs, weather, sales, holidays, closings, etc.
Bulb Size | : | 3/8 in x 2-7/8 in Copper |
Capillary Length | : | 3 in |
Contact Configuration | : | SPST |
Contact Rating | : | 0.25 A at 0.25 to 12 VDC, Full Load: 8 A at 120 VAC, 13 A at 240 VAC, Locked Rotor: 48 A at 120 VAC, 30.6 A at 240 VAC |
Differential Temperature | : | 10 to 25 deg F |
Dimensions | : | 2 W x 8-5/8 in H x 2-1/8 in D |
Mounting Type | : | Horizontal/Vertical |
Temperature Rating | : | 130 to 270 deg F |
Well Spud Size | : | 1/2 in NPT |
Aquastat controllers are immersion type devices for limiting or regulating the temperature of liquids in boilers, storage tanks, and other applications where temperature control is required. Honeywell's L4006 are used in applications that utilize the existing wells.
Honeywell Aquastat, 3/8 in x 2-7/8 in Copper Bulb, 3 in Capillary Length, 1/2 in NPT Well Spud, 0.25 A at 0.25 to 12 VDC, Full Load: 8 A at 120 VAC, 13 A at 240 VAC, Locked Rotor: 48 A at 120 VAC, 30.6 A at 240 VAC Contact, SPST, Horizontal/Vertical Mount, 130 to 270 deg F, 10 to 25 deg F Differential, 2 W x 8-5/8 in H x 2-1/8 in D
- Totally enclosed micro switch snap acting switches operate on temperature rise to setpoint
- Visible control point scale and external adjustments screw permit easy setting
- Horizontal or vertical insertion of the sensing element
- Remote bulb model may be used to sense air temperature in ducts and in outside air sensing applications
- Direct or well immersion of the sensing element
- Includes heat-conductive compound, well adapter